Price_List.pdf
Axxium_Specs.pdf
AXXIUM Specifications
Best Power reserves the right to change specification without prior notice.
Line Transient Protection: Passes ANSI/IEEE C62.41 Category A testing.
Safety Compliance: Model U: Tested to electrical requirements of UL1449; listed to UL1778, and
CAN/CSA C22.2 No. 107.1 M95.
EMC Compliance: Model U: FCC Class A.
Noise (RF) Suppression: Full-time EMI/RFI filtering.
Efficiency: > 87% on-line operation (full load; fully charged, at least 50% load).
Capacity VA/Watts: 1000VA / 700W; 1500VA / 1050W; 2000VA / 1400W; 3000VA / 2100W
Voltage Nominal: Model U: 120 VAC
Voltage Range: Model U: 0 to 160 VAC operating on battery, with 80 to 138 VAC normal input voltage
range.
Frequency: 50/60 Hz auto-sensing 55 – 65 Hz (60 Hz); 45 – 55 Hz (50 Hz) (50/60 Hz +/- 0.5 Hz on
battery.)
Minimum Runtime (minutes): 1000VA: Full load: 9 minutes. Half load: 24 minutes.
1500VA: Full load: 8 minutes. Half load: 23 minutes.
2000VA and 3000VA: No backup time (no internal batteries).
Transfer Time to Bypass: 1000U and 1500U Models: 0-4 ms.
2000U and 3000U Models: No transfer time.
Telephone line surge suppression for U models: per Bellcore 1089: 1.2/50msec waveform +/- 2kV peak,
Compliant to UL497A.
Battery: Sealed, maintenance-free, valve-regulated, UL 924 recognized.
1000 VA Models: Three 12-V, 9 AH batteries. Nominal Voltage is 36 VDC.
1500 VA Models: Four 12-V, 9 AH batteries. Nominal Voltage is 48 VDC.
2000 VA Models: No internal batteries.
3000 VA Models: No internal batteries.
Automatic Battery Test: Automatic battery test occurs upon startup and every 14 days thereafter.
Alarm will sound if the battery fails this test.
Battery Recharge Time (to 95% of capacity): All Models: 8 hours
Overcurrent Protection (on line): All Models: Fuse
AC Input Plug/Cord Information:
1000 U – NEMA 5-15P, cord attached.
1500 U – NEMA 5-15P, cord attached.
2000 U – NEMA 5-20P, cord attached.
3000 U – NEMA L5-30P, cord attached.
AC Output Distribution:
1000 U – (6) NEMA 5-15R
1500 U – (6) NEMA 5-15R
2000 U – (4) NEMA 5-15R
(2) NEMA 5-20R
3000 U – (4) NEMA 5-15R
(1) NEMA L5-30R
Load Compatibility: Can support 100% power factor corrected, switch-mode power supply load.
Audible Noise: <45 dBA at one meter, except 2000 and 3000 VA models which are < 52 dBA at one
meter.
Ventilation: Air around the unit must be free of dust, chemicals, or other materials that corrode or
contaminate. Air must be free to move around the unit.
Operating Temperature: 32o – 104o F (0o – 40o C).
Storage Temperature: 5o – 122o F (-15o to +50o C). Battery life reduced above 77o F (25o C).
If the Axxium Rackmount unit is stored, the batteries should be recharged
every 6 months.
If stored above 77o F (25o C), recharge the batteries more often.
Humidity: 0% - 95% (non-condensing)
Altitude: 3000m (10,000 ft maximum)
Dimension (Height x Width x Depth): All Models: 3.35 x 19 x 19.3 (85.2 x 483 x 490mm)
Weight: 1000: 39.6 lbs. (18.0 kg) 2000: 57.2 lbs. (26.0 kg)
1500: 51.3 lbs. (23.3 kg) 3000: 86.0 lbs. (39.1 kg)